Main power cord requirements

As an installer or user, you must supply the main power cord for your cutting system.

Refer to Input power requirements for recommended main power cord size.

The recommended main power cord sizes are based on Table 310.16 of the U.S. National Electric Code (2023 Handbook). Input power requirements shows stranded-flexible cord rates for 90°C (194°F). The size requirement for the main power cord at your site can change because of the following conditions:
  • Wires with lower temperature ratings
  • Wires with different insulation types
  • Different distances between the line-disconnect switch or receptacle and the plasma power supply
  • Local codes and regulations

The strain relief for the input power cord that comes with the plasma power supply is sized correctly. Speak with a licensed electrician to make sure that your main power cord size and length comply with the codes in your location.

Always follow the national and local electrical safety requirements for your location, including requirements for correct electrical system design and installation and main power cord size and length. Speak with a licensed electrician for more information about the codes in your location.