Low rated electrical power source considerations

Make sure that the electrical service is the correct size to operate the plasma power supply at full output and at its rated duty cycle.

If you operate the plasma power supply on an electrical service that is rated lower than what is recommended in Voltage configurations, it can be necessary to:
  • Decrease the cutting current (amperage setting).
  • Decrease plasma arc stretch. The more you stretch the plasma arc, the more current the system pulls and the more likely you are to overheat the system or trip the circuit breaker.

If you use a 1-phase system with an input voltage of 230 V on a 20 A breaker, the recommended output current is 19 A.

Input voltage 230 V
Input current at rated output (19 A x 155 V = 2.9 kW) 18 A
Input current during arc stretch 19 A
Voltage tolerance +20% to -15%