Connection requirements for electrical power

Use the Hypertherm® input current ratings to determine conductor sizes for power connection and installation instructions.

The Hypertherm ratings are designated HYP on the data plate on the bottom of the plasma power supply. Use the higher HYP input current value for installation purposes. Refer to System specifications on the data plate for a sample data plate.

  • Use a line-disconnect switch for each plasma power supply so that the operator can stop the incoming power quickly in an emergency.

    This image shows a plasma power supply connected to a line disconnect switch.
  • Put the switch in a location where the operator can get access easily. A licensed electrician must install the power switch according to national and local codes.
  • The interrupt level of the switch must equal or be more than the continuous rating of the fuses.
  • The switch must also do the following:
    • Isolate the electrical equipment and disconnect all live conductors from the incoming supply voltage when in the OFF position.
    • Have one OFF and one ON position that are clearly marked with O (OFF) and I (ON).
    • Have an external operating handle that can be locked in the OFF position.
    • Contain a power-operated mechanism that operates as an emergency stop.
    • Have approved time-delay fuses installed. Refer to Voltage configurations for recommended fuse sizes.